  • Upgradation of Control Modules
  • Supply of 1500kVA Module
  • Supply of 500kVA Module
  • Supply of 60kVA Module
  • Installation of modules

Technical Specifications

Upgradation of Control Modules — Supply of 1500kVA Module

Specification
Supply of AMF (Auto Mains Failure) Generator Control Module for the existing 1500 kVA FG Wilson DG Set, Model P1500P3, installed at Main Bank Building, SBP, Karachi (Make: Deep Sea, DEIF, CompAmp or approved equivalent), complete with mains and generator voltage/frequency monitoring, current and power monitoring (kW, kVA, kVAr, power factor), energy monitoring (kWh), USB, RS232, RS485, CAN and expansion communication ports, at least 4-line backlit graphical LCD, event log of at least 250 events, and operating temperature range of -30°C to +70°C. The module should support automatic generator starting and mains failure/changeover functions and shall be supplied complete with all necessary connections and mounting accessories, including a one-year warranty, complete in all respects as directed by the Engineer-in-Charge.

Upgradation of Control Modules — Supply of 500kVA Module

Specification
Supply of AMF (Auto Mains Failure) Generator Control Module for the existing 500 kVA FG Wilson DG Set, Model P550-3, installed at Main Bank Building, SBP, Karachi (Make: Deep Sea, DEIF, CompAmp or approved equivalent), complete with mains and generator voltage/frequency monitoring, current and power monitoring (kW, kVA, kVAr, power factor), energy monitoring (kWh), USB, RS232, RS485, CAN and expansion communication ports, at least 4-line backlit graphical LCD, event log of at least 250 events, and operating temperature range of -30°C to +70°C. The module should support automatic generator starting and mains failure/changeover functions and shall be supplied complete with all necessary connections and mounting accessories, including a one-year warranty, complete in all respects as directed by the Engineer-in-Charge.

Upgradation of Control Modules — Supply of 60kVA Module

Specification
Supply of AMF (Auto Mains Failure) Generator Control Module for the existing 60 kVA diesel generator set with Perkins engine and Mecc Alte alternator, installed at KDA Bungalow, Karachi (Make: Deep Sea, DEIF, CompAmp or approved equivalent), complete with compact enclosure, backlit display, mains and generator voltage/frequency monitoring, generator current and power monitoring (kW, kVA, kVAr, power factor), energy monitoring (kWh, kVAh, kVArh), USB configuration port, J1939/CAN engine communication, and operating temperature range of -30°C to +70°C. The module shall support automatic generator starting and mains failure/changeover functions and shall be supplied complete with all necessary connections and mounting accessories, including a one-year warranty, complete in all respects as directed by the Engineer-in-Charge.

Upgradation of Control Modules — Installation of modules

Specification
Installation, wiring, configuration, parameter setting, testing and commissioning of the supplied generator control modules, including integration with all existing generator sensors, engine controls and associated wiring, complete in all respects as directed by the Engineer-in-Charge.